66 HUNTER-PRO Series Installation Guide
5.6 Key #4: Timers, Counters
Set the system’s timings for entry/exit delays, outputs tripping, faults response and more.
4
NE XT
NEXT
AC Report Delay
ENTER/NEXT/END
Phone Rprt Delay
ENTER/NEXT/END
NE XT
Burg. Rprt.Delay
ENTER/NEXT/END
NEXT
Soak Test Days
ENTER/NEXT/END
NEXT
Double Knock
ENTER/NEXT/END
NE XT
Cond. Zones Time
ENTER/NEXT/END
NEXT
Byps. Limit Time
ENTER/NEXT/END
NEXT
False Code
ENTER/NEXT/END
NE XT
Inactiv. Report
ENTER/NEXT/END
ENTR NE XT
T ime rs, Cou nter s
E NTE R/NEX T/EN D
O utpu t T imes
E NTER/ NEXT /END
NE XT
Ex t. Sir en Tim e
EN TER/ NEXT/ END
5.6.1 Entry/Exit Delays
3
ENTR ENTR
Timers , Cou nters
ENTER/ NEXT/END
Entry/Exit Delay
ENTER/NEXT/END
Entry 1 2 Ex it
2 0 20 6 0
Set ‘Entry 1’ delay for all the zones (To use the ‘Entry 2’, refer to section 5.4.1,
parameter ‘T’) and the exit delay. Default entry delay is 20 seconds; exit, 60 seconds.
5.6.2 Output Times
Set the outputs type timing, i.e., the time in which the related PCB output is tripped. In
each output type screen press [ENTR] and set the time.
The HUNTER-PRO series has 3 trip times:
1. ‘0’: The output is tripped until the system is disarmed
2. 1-9998: The output is tripped for this time (in seconds)
3. 9999: The output is tripped for as long as the event (By an output type. see
further) that had triggered it exists. For example, the onboard relay is triggered by
and for as long a phone line failure remains. As soon as the fault is resolved the
output is switched off.