HUNTER-PRO Series Installation Guide 87
7.3 Additional Faults
7.3.1 MS Comm. Fault
The system has preset to test all aspects of communication to MS: Press [6] for 2
seconds and enter technician code. All testing process will be displayed on the keypad.
7.3.2 MS Radio Fault
Make sure that:
1. The wiring between system and radio receiver is ok.
2. Radio account no. is other than ‘0’.
3. Comm. format is compatible with the one used in the MS
4. The receiver’s antenna is intact, not bended and is attached vertically.
5. If the antenna is installed on a separate surface, check its wires.
7.3.3 Private Dialer Fault
Make sure that:
1. The telephone line is properly connected to the LINE terminal blocks.
2. At least one private telephone number is programmed.
3. Correct telephone numbers have been entered
4. In Communication menu the “P” for telephone is set to “+”.
5. In Communication/Private Dialer menu the parameters are programmed.
6. If the system is connected to an extension of a private switchboard a prefix has
been programmed.
Disarming immediately after alarm will stop the dialer. To test the
dialer, arm the system and wait for dialing
7.3.4 Incoming Calls Fault
If the system does not receive calls, make sure that:
1. In Communication menu (section. 5.4) the “P” for telephone is set to “+”.
2. The programmed number of rings exceeds its limit.
3. The telephone line is properly connected to the LINE terminal blocks.
7.3.5 Tamper
TAMPER 1: Tamper 1 is triggered.
TAMPER 2: Tamper 2 is triggered.