PE6000 User Manual Function Code Tables
55
Group F5: Output Terminals
Function
Code
Parameter Name Setting Range Default
Property
P5-00
FM terminal output
mode
0: Pulse output (FMP)
1: Switch signal output (FMR)
0
P5-01
FMR function
(open- collector
output terminal)
0: No output
1: AC drive running
2: Fault output (stop)
3: Frequency-level detection PDT1 output
4: Frequency reached
5: Zero-speed running (no output
at stop)
6: Motor overload pre-warning
7: AC drive overload pre-warning
8: Set count value reached
9: Designated count value reached
11: PLC cycle complete
12: Accumulative running time reached
13: Frequency limited
14: Torque limited
15: Ready for RUN
16: AI1 larger than AI2
17: Frequency upper limit reached
18: Frequency lower limit reached (no
output at stop)
19: Undervoltage state output
20: Communication setting
23: Zero-speed running 2 (having output at
stop)
24: Accumulative power-on time reached
25: Frequency level detection PDT2 output
26: Frequency 1 reached
27: Frequency 2 reached
28: Current 1 reached
29: Current 2 reached
30: Timing reached
31: AI1 input limit exceeded
32: Load becoming 0
33: Reverse running
34: Zero current state
35: Module temperature reached
36: Software current limit
exceeded
37: Frequency lower limit reached (having
output at stop) 38: Alarm output
39: Motor overheat warning
40: Current running time reached
41: Fault output (There is no output if it is
the coast to stop Fault and undervoltage
occurs.)
0
P5-02
Relay function
(T/A-T/B-T/C)
2
P5-04
DO1 function
selection (open-
collector output
terminal)
0