Function Code Tables PE6000 User Manual
62
Function
Code
Parameter Name Setting Range Default Property
P8-50
Wakeup delay time 0.0–6500.0s 0.0s
☆
P8-51
Dormant frequency
0.00 Hz to wakeup frequency
(P8-49)
0.00 Hz
☆
P8-52
Dormant delay time 0.0–6500.0s 0.0s
☆
P8-53
Current running time
reached
0.0–6500.0 min 0.0 min
☆
Group P9: Fault and Protection
P9-00
Motor overload protection
selection
0: Disabled
1: Enabled
1
☆
P9-01
Motor overload protection
gain
0.20–10.00 1.00
☆
P9-02
Motor overload warning
coefficient
50%–100% 80%
☆
P9-03
Overvoltage stall gain 0 (no stall overvoltage)–100 0
☆
P9-04
Overvoltage stall
protective voltage
120%–150% 130%
☆
P9-05
Overcurrent stall gain 0–100 20
☆
P9-06
Overcurrent stall
protective current
100%–200% 150%
☆
P9-07
Short-circuit to ground
upon power-on
0: Disabled
1: Enabled
1
☆
P9-09
Fault auto reset times 0–20 0
☆
P9-10
DO action during fault
auto reset
0: Not act
1: Act
0
☆
P9-11
Time interval of fault auto
reset
0.1s–100.0s 1.0s
☆
P9-12
Input phase loss
protection/ contactor
energizing protection
selection
0: Disabled
1: Enabled
11
☆
P9-13
Output phase loss
protection selection
0: Disabled
1: Enabled
1
☆