Function Code Tables PE6000 User Manual
66
Function
Code
Parameter Name Setting Range Default
Property
PA-01
PID digital setting 0.0%–100.0% 50.0%
PA-02
PID feedback source
0: AI1
1: AI2
2: Keyboard potentiometer
3: AI1 – AI2
4: Pulse setting (DI5)
5: Communication setting
6: AI1 + AI2
7: MAX (|AI1|, |AI2|)
8: MIN (|AI1|, |AI2|)
0
PA-03
PID action direction
0: Forward action
1: Reverse action
0
PA-04
PID setting feedback
range
0–65535 1000
PA-05
Proportional gain Kp1 0.0–100.0 20.0
PA-06
Integral time Ti1 0.01–10.00s 2.00s
PA-07
Differential time Td1 0.00–10.000 0.000s
PA-08
Cut-off frequency of PID
reverse rotation
0.00 to maximum frequency 2.00Hz
PA-09
PID deviation limit 0.0%–100.0% 0.0%
PA-10
PID differential limit 0.00%–100.00% 0.10%
PA-11
PID setting change time
0.00–650.00s 0.00s
PA-12
PID feedback filter time 0.00–60.00s 0.00s
PA-13
PID output filter time 0.00–60.00s 0.00s
PA-14
Reserved - -
PA-15
Proportional gain Kp2 0.0–100.0 20.0
PA-16
Integral time Ti2 0.01–10.00s 2.00s
PA-17
Differential time Td2 0.000–10.000s 0.000s
PA-18
PID parameter
switchover condition
0: No switchover
1: Switchover via DI
2: Automatic switchover based on
deviation
0
PA-19
PID parameter
switchover deviation 1
0.0% to PA-20 20.0%
PA-20
PID parameter
switchover deviation 2
PA-19 to 100.0% 80.0%
PA-21
PID initial value 0.0%–100.0% 0.0%