Function Code Tables PE6000 User Manual
74
Function
Code
Parameter Name Setting Range Default Property
A6-25
Jump amplitude of AI1 input
corresponding setting
0.0%–100.0% 0.5%
A6-26
Jump point of AI2 input
corresponding setting
-100.0%–100.0% 0.0%
A6-27
Jump amplitude of AI2 input
corresponding setting
0.0%–100.0% 0.5%
Group A8: Point-point Communication
A8-00
Point-point communication
selection
0: Disabled
1: Enabled
0
A8-01
Master and slave selection
0: Master
1: Slave
0
A8-02
Source selection of data
from master
0: Output torque
1: Running frequency
2: Setting frequency
3: Feedback rate
011
A8-03
Usage of data received by
slave
0: Torque setting
1: Frequency setting
0
A8-04
Zero offset of received data
(torque)
-100.00%–100.00% 0.00%
A8-05
Gain of received data
(torque)
-10.00–10.00 1.00
A8-06
Point-point communication
interruption detection time
0.0–10.0s 1.0s
A8-07
Master data sending cycle
0.001–10.000s 0.001s
Group AC: AI/AO Correction
AC-00
AI1 measured voltage 1 0.500–4.000 V
Factory
corrected
AC-01
AI1 displayed voltage 1 0.500–4.000 V
Factory
corrected
AC-02
AI1 measured voltage 2 6.000–9.999 V
Factory
corrected
AC-03
AI1 displayed voltage 2 6.000–9.999 V
Factory
corrected
AC-04
AI2 measured voltage 1 0.500–4.000 V
Factory
corrected
AC-05
AI2 displayed voltage 1 0.500–4.000 V
Factory
corrected
AC-06
AI2 measured voltage 2 6.000–9.999 V
Factory
corrected
AC-07
AI2 displayed voltage 2 6.000–9.999 V
Factory
corrected

Table of Contents