1514
within which the refrigerant containing parts are
installed;
The ventilation machinery and outlets are operating
adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the
secondary circuit shall be checked for the presence
of refrigerant; Marking to the equipment continues
to be visible and legible. Markings and signs that are
illegible shall be corrected;
Refrigeration pipe or components are installed in a
position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing
components, unless the components are constructed
of materials which are inherently resistant to being
corroded or are suitably protected against being so
corroded.
9) Checks to electrical devices
Repair and maintenance to electrical components
shall include initial safety checks and component
inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be
connected to the circuit until it is satisfactorily dealt
with. If the fault cannot be corrected immediately
but it is necessary to continue operation, an adequate
temporary solution shall be used. This shall be
reported to the owner of the equipment so all parties
are advised.
Initial safety checks shall include: