MPK with CommandPak
Control System BACnet /IP User’s Guide
5 – Supply air CFM
6 – Exhaust air CFM
7 – Purge air CFM
8 – Outside air CFM
9 – Supply fan current signal
10 – Exhaust fan current signal
11 – Purge fan current signal
13 – Pool 1 temperature
14 – Pool water circuit A pressure drop
15 – Pool 2 temperature
16 – Pool water circuit B pressure drop
19 – Air off evaporator temperature
20 – Air off evaporator humidity
22 – Evaporator bypass damper position feedback
24 – Outside air damper position feedback
25 – Recirc air damper position feedback
26 – Space pressure
27 – Return air CO2 level
28 – Surface temperature
29 – Outside air filter pressure drop
30 – Return air filter pressure drop
UNIT FAULT CODE AND LAST UNIT FAULT CODE (XWIUNITGNLFLTCODE)
AV1022 and AV1024 are enumerated values indicating a general fault condition for the unit. The last fault (AV1022)
indicates the most recent previous fault condition for the unit. The value for these objects is decoded as follows:
0 – Normal
1 – Coil freeze warning active
2 – Fire trip mode active
3 – Smoke purge mode active
4 – Supply fan not running
5 – Exhaust fan not running
6 – Purge fan not running
7 – Exhaust fan VFD fault active
8 – Supply fan VFD fault active
9 – Purge fan VFD fault active
10 – System startup active Normal for 5 minutes after power on.
11 – Supply fan deadheaded. Supply fan requested on with both outside air and recirc air dampers less than
25% open.
12 – Aux heating system failure
13 – Aux cooling system failure
14 – Compressor Module 1 fault active
15 – Compressor Module 2 fault active
16 – Compressor Module 3 fault active