57EGW05-SWHPEG-20140724
TM
TM
104. Purge - Purge Mode Status (SR, SEP only)
CM2 Ver - ECC Control Module 2 Software Version Number
CM3 - ECC Control Module 3 Software Version Number
CM4 - ECC Control Module 4 Software Version Number
CM5 - ECC Control Module 5 Software Version Number
124. ACC #1 Stat - System 1 Air Cooled Condenser Status
125. ACC #2 Stat - System 2 Air Cooled Condenser Status
140. Cpr 1 Mode - System 1 Mode of Operation
141. Cpr 2 Mode - System 2 Mode of Operation
142. Occ_Flag - Occupancy Mode
170. Fault Cnt 1 - System 1 Compressor Fault Count Since Last Reset
171. Fault Cnt 2 - System 2 Compressor Fault Count Since Last Reset
172. Exh Dpr - Actual Exhaust or Purge Air Damper Position
173. Rcrc Dpr - Actual Recirculation or Bypass air Damper Position
174. Outs Dpr - Actual Outside Air Damper Position
175. Des Dpr - Desired Outside Air Damper Position (SR only)
176. Min D Alw - Minimum Damper Position Setpoint (SR only)
177. Max D Alw - Maximum Damper Position Setpoint (SR only)
178. Economiz - Economizer Status (SR & SEP only)
180. Aux Air Ht - Auxiliary Air Heating Stages Active
181. Aux Wtr 1 - Pool 1 Auxiliary Water Heater Status
182. Aux Wtr 2 - Pool 2 Auxiliary Water Heater Status
183. Flywhl Act - Flywheel Cooling Status
184. Cpr1 Remain - System 1 Anticycle Time Remaining
185. Cpr2 Remain - System 2 Anticycle Time Remaining
Sply Fan Curr - Supply Fan Motor Current
Rtn Fan Curr - Return Fan Motor Current (SR only)
Cmpr 1 Curr - System 1 Compressor Current
Cmpr 2 Curr - System 2 Compressor Current
Dpr Limit Code - Damper Position Limit Code (SR only)
FzyDprChg - Fuzzy Logic Mixing Box Control Output (SR only) 0.0 - 150.0
FzyRatCprChg - Fuzzy Logic Space Temperature Control Variable 0.0 - 200.0
FzyDptCprChg - Fuzzy Logic Dew Point Control Variable 0.0 - 200.0
SF Econo Actv – Single Fan Economizer Active? (SEP only)
Network Unit Status – Displays if unit ID 1-5 are ONLINE or OFFLINE. (Network installations only)
Network Role – Displays if the unit is operating in the master or slave role. (Network installations only)
Unit ID Number – Read only. Displays the unit ID that is currently displayed (1-5)