Chapter 5 Function parameter
58
Code
Parameter name
Setting range
Factory
default
Change
0
No output
The function of Output terminal is disabled.
1
Motor is running
forward
Inverter Run Forward: when the inverter
runs forward, if the frequency output exists,
ON signal will output.
2
Motor is running
reverse
Inverter Run Reverse: when the inverter
runs reverse, if the frequency output exists,
ON signal will output.
3
Fault output
Fault Output: When the inverter occurs
failure, and outputs ON signal.
4
Frequency level
detection FDT output
For the frequency level detection FDT
arrival, please refer to refer to the details on
the function code F7.10, F7.11.
5
Frequency arrival
For the frequency arrival, please refer to the
details on the function code F7.12.
6
Zero speed running
Zero Speed Running: if the output
frequency and the setting frequency of
inverter are simultaneously zero, ON signal
will output.
7
Upper limit frequency
arrival
Upper Limit Frequency Arrival (F0.10) :
Outputs ON signal when the operating
frequency reaches the upper limit
frequency,
8
Lower limit frequency
arrival
Lower Limit Frequency Arrival (F0.11) :
Outputs ON signal when the operating
frequency reaches the lower limit
frequency,
9 to 10
Reserved
F2.04
AO1 output selection
0: Running
frequency
1: Set frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
6: Analog input AI1
value
7: Analog input AI2
value
8: Run speed
9 to 10: Reserved
0
The standard analog output is 0 to 20mA (or 0 to 10V), the jumper JP4 can be used to
choose current or voltage output. For the corresponding amount, see the below table:
Set
value
Function
Description