F4.03 to F4.08 six parameters are used to define multi-point V/F curve.
The multi-point V/F curve is set according to the load characteristics of motor, please
be noted that the relationship between three voltage points and three frequency points
must be meet: V1 <V2 <V3, F1 <F2 <F3. The setting of multi-point V/F curve is as
shown in below figure.
In the sate of low frequency, if the voltage is set to a higher value, which may cause
motor overheating even burned, the inverter may appear overcurrent stall or
overcurrent protection.
V1 to V3: voltage percentage of the 1st to 3rd stages of multi-speed; F1 to F3:
frequency percentage of the 1st to 3rd stages of multi-speed; Vb: motor rated voltage;
Fb motor rated operating frequency.