Chapter 2 Standard specifications
8
Chapter 2
PI160-0R7G3Z
PI160-1R5G3Z
PI160-2R2G3Z
PI160-3R7G3Z
2-3.Standard specifications
Items
Specifications
Power
Voltage and frequency
levels
Single-phase 220V, 50/60Hz;
Three-phase 220V, 50/60Hz;
Three-phase 380V, 50/60Hz
Allowable fluctuation
Voltage:±10%; Frequency:±5%
Voltage unbalance rate is less than 3% , Aberration rate
meet IEC61800-2 standard
Control system
Control system
High performance vector control inverter based on DSP
Control method
V/F control, vector control W/O PG,
Automatic torque boost
function
Realize low frequency (1Hz) and large output torque
control under the V/F control mode.
Acceleration/deceleratio
n control
Straight or S-curve mode. Four times available and time
range is 0.0 to 6500.0s.
V/F curve mode
Linear, square root/m-th power, customized definition V/F
curve
Over load capability
G type: Rated current 150% - 1 minute, rated current
180% - 2 seconds
Maximum frequency
Vector control:0 to 300Hz
V/F control:0 to 3200Hz
Carrier Frequency
0.5 to 16kHz; automatically adjust carrier frequency
according to the load characteristics.
Input frequency
resolution
Digital setting: 0.01Hz Analog setting: maximum
frequency 0.01Hz
Start torque
G type: 0.5Hz/150% (vector control W/O PG)
Speed range
1:100 (vector control W/O PG)
Steady-speed precision
Vector control W/O PG: ≤ ± 0.5% (Rated synchronous
speed)
Torque response
≤ 40ms (vector control W/O PG)
Torque boost
Automatic torque boost; manual torque boost(0.1% to
30.0%)
DC braking
DC braking frequency: 0.0Hz to max. frequency, braking
time:
0.0 to 100.0 seconds, braking current value: 0.0% to
100.0%
Jogging control
Jog Frequency Range: 0.00Hz to max. frequency;
Jog Ac/deceleration time: 0.0s to 6500.0s
Multi-speed operation
Achieve up to 16-speed operation through the control
terminal
Built-in PID
Easy to realize closed-loop control system for the process
control.
Automatic voltage
regulation(AVR)
Automatically maintain a constant output voltage when
the voltage of electricity grid changes
Torque limit and control
"Excavator" feature - torque is automatically limited
during the operation to prevent frequent over current trip;
the closed-loop vector mode is used to control torque.