0.1 to 30%
119
F4.02
Torque boost cut-off frequency
0.00Hz to F0.19(Maximum
frequency)
15
.
00
Hz
120
F4.03
Multipoint V/F frequency
point 1
0.00Hz to F4.05
0.00Hz
121
F4.04
Multipoint V/F voltage point 1
0.0% to 100.0%
0.0%
122
F4.05
Multipoint V/F frequency
point 2
F4.03 to F4.07
0.00Hz
123
F4.06
Multipoint V/F voltage point 2
0.0% to 100.0%
0.0%
124
F4.07
Multipoint V/F frequency
point 3
F4.05 to b0.04 (Rated motor
frequency)
0.00Hz
125
F4.08
Multipoint V/F voltage point 3
0.0% to 100.0%
0.0%
126
F4.09
Slip compensation coefficient
0% to 200.0%
0
.
0%
127
F4.10
Overexcitation gain
0 to 200
64
128
F4.11
Oscillation suppression gain
0 to 100
-
129
F4.12
V/F separation voltage source
0 to 9
0
130
F4.13
V/F separation voltage digital
setting
0V to rated motor voltage
0V
131
F4.14
V/F separation voltage rise
time
0.0s to 1000.0s
0.0s
5-1-7.F5 Group - Vector control parameters
No.
Code
Parameter name
Setting range
Factory
setting
Chang
e
132
F5.00
Proportion of speed loop
G1
1 to 100
30
133
F5.01
Speed loop low integral time T1
0.01s to 10.00s
0.50s
134
F5.02
Switching frequency 1
0.00 to F5.05
5.00Hz
135
F5.03
Proportion of speed loop
G2
0 to 100
20
136
F5.04
Speed loop high integral time T2
0.01s to 10.00s
1.00s
137
F5.05
Switching frequency 2
F5.02 to F0.19
(Max.frequency)
10.00Hz
138
F5.06
Speed loop integral attribute
0:Valid; 1:Invalid
0
139
F5.07
Torque limit source under speed control
mode
Options 0-5
0
140
F5.08
Upper limit digital setting for lower
torque under speed control mode
0.0% to 200.0%
150
.
0%