Chapter 5 Function parameter
36
Chapter 5
228
F8.19
Fault protection action
selection 3
Units digit:User-defined fault
1(Err.27)(Same as F8.17 units digit)
Tens digit: User-defined fault
2(Err.28)(Same as F8.17 units digit)
Hundreds digit: Power-on time
arrival (Err.29)(Same as F8.17 units
digit)
Thousands digit: Load drop (Err.30)
0: Free stop
1: Deceleration parking
2: Deceleration up to 7% of the rated
motor frequency, and then continue
running,
automatically restore to the set
frequency for when the load drop
does not happen.
Ten thousands digit: PID feedback
loss when running (Err.31)(Same as
F8.17 units digit)
00000
229
F8.20
Fault protection action
selection 4
Units digit: Too large speed deviation
(Err.42)(Same as F8.17 units digit)
Tens digit: Motor overspeed (Err.43)
Hundreds digit: Initial position error
(Err.51)
( same as F8.17 units digit)
Thousands digit: Reserved Ten
thousands digit: Reserved
00000
230
F8.24
Continue running
frequency selection
when failure happens
0: Running at current frequency
1: Running at set frequency
2: Running at upper limit frequency
3: Running at lower limit frequency
4: Running at abnormal spare
frequency
0
231
F8.25
Abnormal spare
frequency
60.0% to 100.0%
100%
232
F8.26
Momentary power cut
action selection
0: Invalid; 1: Deceleration
2: Deceleration and stop
0
233
F8.27
Recovery judgment
voltage of momentary
power cut
50.0% to 100.0%
90%
234
F8.28
Recovery voltage
judgment time of
momentary power cut
0.00s to 100.00s
0.50s
235
F8.29
Judgment voltage of
momentary power cut
action
50.0% to 100.0% (Standard bus
voltage)
80%
236
F8.30
Load drop protection
selection
0: Invalid
1: Valid
0