Chapter 5 Function parameter
35
Chapter 5
218
F8.04
Motor overload pre-
alarm coefficient
50% to 100%
80%
219
F8.05
Overvoltage stall gain
0 to 100
0
220
F8.06
Overvoltage stall
protection voltage /
energy consumption
brake voltage
120% to 150%
130%
221
F8.08
Output phase loss
protection selection
0: Disable
1: Enable
1
222
F8.09
Short to ground
protection
0:Invalid;
1: Valid
1
223
F8.10
Number of automatic
fault reset
0 to 32767
0
224
F8.11
Fault DO action
selection during
automatic fault reset
0: OFF
1: ON
0
225
F8.12
Automatic fault reset
interval
0.1s to 100.0s
1.0s
226
F8.17
Fault protection action
selection 1
Units digit: Motor overload (Err.11)
0: Free stop
1: Stop at the selected mode
2: Continue to run
Tens digit: input phase loss (Err.12)
(Same as units digit)
Hundred digit: Output phase loss
(Err.13) (Same as units digit)
Thousand digit: External fault
(Err.15) (Same as units digit)
Ten thousands digit: Communication
abnormal( Err.16)(Same as units
digit)
00000
227
F8.18
Fault protection action
selection 2
Units digit: Encoder/PG card
abnormal (Err.20)
0: Free stop
1:Switch to V/F and then stop at the
selected mode
2:Switch to V/F and continue to run
Tens digit: function code read and
write abnormal (Err.21)
0: Free stop
1: Stop at the selected mode
Hundreds digit: Reserved
Thousands digit: Motor overheating
(Err.25)(Same as F8.17 units digit)
Ten thousands digit: Running time
arrival(Err.26)( same as F8.17 units
digit)
00000