EasyManua.ls Logo

Powtran PI500 004G3 - Page 35

Powtran PI500 004G3
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Function parameter
31
Chapter 5
10: analog quantity AI3 setting
47
F0.04
Frequency source
auxiliary setting
The same as F0.03
0
48
F0.05
Reference object
selection for frequency
source auxiliary setting
0. relative to maximum frequency
1.relative to master frequency source 1
2. relative to master frequency source 2
0
49
F0.06
Frequency source
auxiliary setting range
0% to 150%
100%
50
F0.07
Frequency source
superimposed selection
Units digit: frequency source selection
Tens digit: arithmetic relationship of
master and auxiliary for frequency
source
00
51
F0.08
Fr
equency source offset
frequency when
superimposing
0.00Hz to F0.19(maximum frequency)
0
.
00Hz
52
F0.09
Shutdown memory
selection for digital set
frequency
0: W/O memory
1: With memory
1
53
F0.10
Frequency command UP
/ DOWN reference when
running
0: Running frequency
1: Set frequency
0
54
F0.11
Command source
selection
0.Keyboard control (LED off)
1.Terminal block control (LED on)
2.Communications command control
(LED flashes)
3. Keyboard control+ Communications
command control
4. Keyboard control+ Communications
command control+ Terminal block
control
0
55
F0.12
Binding frequency
source for command
source
Units digit: binding frequency source
selection for operation panel command
0: no binding;
1. Keyboard setting frequency;
2: analog quantity AI1 setting
3: analog quantity AI2 setting
4: panel encoder setting
5: high speed pulse setting
6: multi-speed setting
7: simple PLC setting
8: PID setting
9: communication given
Tens digit: terminal command binding
frequency source selection (0 to 9, same
as units digit)
Hundreds digit: communication
command binding frequency source
selection (0 to 9, same as units digit)
000
56
F0.13
Acceleration time 1
0.00s to 6500s
Depends
on models

Table of Contents