EasyManua.ls Logo

Powtran PI500 110G3 - External Analog Speed Control (0-10 V)

Powtran PI500 110G3
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix V
104
Appendix V
F1.10
Terminal command mode
Three-wire control mode 1
2
F1.00
DI1 terminal function selection
Forward run (FWD)
1
F1.01
DI2 terminal function selection
Three-wire operation control
3
F1.02
DI3 terminal function selection
Reverse run(REV)
2
F1.03
DI4 terminal function selection
terminal UP
6
F1.04
DI5 terminal function selection
terminal DOWN
7
F1.11
Terminal UP/DOWN change rate
Used to set terminal UP/DOWN
adjustment frequency, the rate of
frequency change.
1.00Hz/s
F0.10
UP/DOWN reference
Running frequency
0
V-9. External analog speed control (external 0 ~ 10V voltage
signal given)
V-9-1 electrical diagram:
Circuit breaker
380V 50/60Hz
Three phase input power supply
Motor
%
M
0+10V DC
(Default)
FWD/STOP
REV/STOP
External simulation speed regulation
(External 0 ~ 10V voltage signal given)
0 ~ 10V Analog signal
V-9-2 Connection:
The (+) terminal of the external analog signal is connected to the AI1 terminal,
and the other terminal of the signal is connected to the GND terminal of the inverter.
V-9-3 Parameter setting:
No.
Code
Parameter name
Setting range
F0.03
Frequency source master setting
AI1analog quantity setting
2
F0.11
Command source selection
Terminal block control (LED on)
1
F1.00
DI1 terminal function selection
Forward run (FWD)
1
F1.01
DI2 terminal function selection
Reverse run(REV)
2
V-10. External analog speed control (external 0 ~ 20mA
current signal given)

Table of Contents

Related product manuals