Chapter 5 Function parameter
37
Chapter 5
112
F1.41
Keyboard Encoder X1
0100.00%
0.00%
113
F1.42
Keyboard Encoder X2
0100.00%
0.50%
114
F1.43
Keyboard Encoder set value
0100.00%
-
115
F1.44
Keyboard Encoder X1
corresponding value Y1
-100.00%+100.00%
0.00%
116
F1.45
Keyboard Encoder X2
corresponding valueY2
-100.00%+100.00%
100.00%
117
F1.46
Keyboard Encoder
control
Bits:
0: Power down protection
1: Power down zero clear
Ten bits:
0: Stop keep
1: Stop order zero clear
2: Stop over zero clear
Hundred bits: reserve
Thousand bits: reserve
00
5-1-4.F2 Group - Output terminals group
No.
Code
Parameter name
Setting range
Factory
setting
Chan-
ge
118
F2.00
SPB terminal output mode selection
0 to 1
0
119
F2.01
Switching quantity output function
selection
0 to 40
0
120
F2.02
Relay 1 output function selection
(TA1.TB1.TC1)
2
121
F2.03
Undefined
122
F2.04
SPA output function selection
(collector open circuit output
terminals)
1
123
F2.05
Relay 2 output function selection
(TA2.TB2.TC2)
1
Above 5 function code is used to select five digital output function. Multifunctional output
terminal functions are as follows:
Setting
value
Functions
Description
0
No output
No output action
1
Inverter running
Inverter is in running state, the output frequency (can be
zero), the output ON signal.
2
Fault output (fault
down )
When the drive fails and downtime, the output ON signal.
3
Frequency level
detection FDT1 output
Please refer to the function code F7.23, F7.24's
instructions.
4
Frequency arrival
Please refer to the description of function code F7.25.
5
Zero-speed running (no
output when shutdown)
Inverter operation and the output frequency is 0, output
ON signal. When the drive is shut down, the signal is
OFF.