EasyManua.ls Logo

Powtran PI500 2R2G3 - 5-1-11 F9 Group - Communication Parameter; 5-1-12 FA Group - Torque Control Parameters

Powtran PI500 2R2G3
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Function parameter
49
Chapter 5
momentary power cut
285
F8.29
Judgment voltage of
momentary power cut
action
50.0% to 100.0% (standard bus
voltage)
10%
286
F8.30~
F8.32
Reserved
287
F8.33
motor temperature
sensor type
0: Invalid;1:PT100 detect
0
288
F8.34
motor over heat
protection value
0200
110
289
F8.35
motor over heat alma
value
0200
90
5-1-11.F9 Group - Communication parameter
No.
Code
Parameter name
Setting range
Factory
setting
Chan-
ge
290
F9.00
Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
291
F9.01
Data format
0: no parity (8-N-2) 2: odd parity (8-O-1)
1: even parity (8-E-1); 3: no parity (8-N-1)
0
292
F9.02
This unit address
1-250, 0 for broadcast address
1
293
F9.03
Response delay
0ms-20ms
2ms
294
F9.04
Communication
timeout time
0.0(Invalid)0.1~60.0s
0.0
295
F9.05
Data protocol selection
Units digit: MODBUS
0: non-standard MODBUS protocol
1: standard MODBUS protocol
Tens digit: Profibus-DP
0: PP01 format
1: PP02 format
2: PP03 format
3: PP05 format
31
296
F9.06
Current resolution
0: 0.01A 1: 0.1A
0
297
F9.07
Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
5-1-12.FA Group - Torque control parameters
No.
Code
Parameter name
Setting range
Factory
setting
Chan-
ge
298
FA.00
Speed/torque control mode
selection
0: speed control 1: torque
control
0
299
FA.01
Torque setting source selection
under torque control mode
0: keyboard setting (FA.02)
1: Analog AI1 setting
2: Analog AI2 setting
0

Table of Contents