Chapter 5 Function parameter
31
Chapter 5
As a high-speed pulse output, the maximum frequency of the output pulse is 100kHz, high-
speed pulse output of the correlation function refer to Note F2.06.
F2.01
Switching quantity output function
selection (Open collector output
terminal)
0~40
0
F2.02
Relay 1 output function selection
(TA1.TB1.TC1)
0~40
2
F2.03
Undefined
F2.04
SPA output function selection (collector
open circuit output terminals)
0~40
1
F2.05
Relay 2 output function selection
(TA2.TB2.TC2)
0~40
1
Above 5 function code is used to select five digital output function. Multifunctional output
terminal functions are as follows:
Seting
value
Functions
Description
0
No output
No output action
1
Inverter running
Inverter is in running state, the output frequency (can be
zero), the output ON signal.
2
Fault output (fault down )
When the drive fails and downtime, the output ON signal.
3
Frequency level detection
FDT1 output
Please refer to the function code F7.23, F7.24's
instructions.
4
Frequency arrival
Please refer to the description of function code F7.25.
5
Zero-speed running (no
output when shutdown)
Inverter operation and the output frequency is 0, output
ON signal.When the drive is shut down, the signal is OFF.
6
Motor overload pre-alarm
Before the motor overload protection, according to the
overload pre-alarm threshold value judgment, more than
the pre-alarm threshold value output ON signal. Motor
overload parameter settings refer to the function code
F8.02 ~ F8.04.
7
Inverter overload pre-alarm
Before the inverter overload occurs 10s, output ON
signal.Setup counter arrive
11
PLC cycle is complete
After simple PLC completes one cycle, the output of a
pulse width of 250ms signal.
12
Total running time arrival
Inverter total running time of more than F7.21 F6.07 set
time,the output ON signal.
13
Limited in frequency
When the set frequency exceeds the upper limit frequency
or lower frequency, and output frequency is beyond the
upper limit frequency or lower limit frequency, output ON
signal.
14
Torque limiting
Drive under the speed control mode, when the output
torque reaches the torque limit, the inverter is stall
protection status, while the output ON signal.
15
Ready to run
When the inverter main circuit and control circuit power
supply has stabilized, and the drive does not detect any
fault information, the drive is in an operational state,
output ON signal.
16
AI1>AI2
When the value of the analog input AI is greater than the
value of AI2 input and output ON signal.