Chapter 5 Function parameter
36
0
1
2
3
4
5
6
7
8
910
11
121314
15
DI input status
Bus voltage
(V)
Set frequency
DO output status
AI1 Voltage(V)
(Hz)
Numerical value
Length
Load speed
PID setting
PLC range
High-speed pulse input frequency(Hz)
Reverse
Reverse
Reverse
AI2 Voltage(V)
AI3 Voltage(V)
If the above parameters need to be displayed on operation, firstly set its position to 1, and then
set at F6.03 after converting the binary number to the hexadecimal number.
Inverter module
radiator temperature
Display the inverter module IGBT temperature.The different models of the inverter module
vary IGBT overtemperature protection values.
Display the total run time of inverter When the run time reaches the set time(F7.21), the
inverter's multi-function digital output function (12) outputs ON signal.
Show the total time of inverter power-on, When the power-on time reaches the set
time(F7.20), the inverter’s multi-function digital output function(24) outputs ON signal.
Control panel software version number
When dormancy function Settings (F6.13 = 1) are valid, E0.03 (wake delay time), E0.09
(dormancy frequency), and E0.11 (dormancy delay time) function are available.
0:Small keyboard(Single row LED)
1:Large Keyboard(Double row LED)
The parameter of motor selection2 can be showed in the bottom of double LED or LCD.
Power correction coefficient
Frequency converter with motor running, the display output power(d0.05)is different with the
actual output power, through the parameters, adjust the converter display power and the actual
output power corresponding relation.
STOP/RESET/ key and encoder is enabled
RUN/STOP/UP/DOWN key is enabled
Pressing the PRG+ Encoder keys to achieve lock and unlock. When the keyboard belongs to
the lock state, when the keyboard is locked, the digital display tube will show "A." in front, such as
the keyboard on display 50, when the lock, press the keyboard "PGR" key, digital display "A.50.00.
QUICK key function
selection