Chapter 5 Function parameter
26
Chapter 5
V/F control
2
0:Vector control without PG
Refers to the open-loop vector control for high-performance control applications typically ,
only one inverter to drive a motor.
1:Reserved
2:V/F control
Suitable for less precision control applications, such as fan and pump loads. Can be used for
an inverter drives several m`otors occasions.
Note: Vector control mode, the drive capacity and the level of motor capacity difference
can’t be too large, the drive motor can power level than the big two or a small one, otherwise it
may result in degradation of the control performance or the drive system does not work properly.
F0.01
Keyboard set
frequency
0.00Hz~F0.19(maximum frequency)
50.00Hz
F0.03
Frequency source
master setting
Frequency setting by Keyboard
(F0.01,UP/DOWN can be modified, power-
down without memory)
0
8
Frequency set by Keyboard (F0.01,UP/DOWN
can be modified, power-down without memory)
1
Analog AI1 setting
2
Analog AI2 setting
3
Panel potentiometer setting
4
High-speed pulse setting
5
Multi-speed operation setting
6
Simple PLC program setting
7
PV setting
8
PID control setting
Remote communications setting
9
Analog AI3 setting
10
Select inverter master reference frequency input channels. There are 10 master reference
frequency channels in all:
8:PV setting/PID control setting
(1)PV setting, Solar pump functions is effective when E0 group of Solar pump special group
select 1 or 2, It’s belong to PID control setting if not setting E0.00=1 or 2.
(2) Select process PID control output as the operating frequency. Generally it is used for
closed-loop control, such as constant pressure closed-loop control, constant tension closed-
loop control, solar pump dedicated and other occasions.
Select PID as the frequency source, you need to set E2 group "PID function"parameters.
F0.11
Command source
selection
Keyboard control (LED off)
0
4
Terminal block control (LED on)
1
Communications command control (LED
flashes)
2
Keyboard control+ Communications
command control
3
Keyboard control+ Communications
commandcontrol+ Terminal block control
4
F0.13
Acceleration time1
0.0s~6500s
-
F0.14
Deceleration time1
0.0s~6500s
-