Chapter 5 Function parameter
32
When the operating frequency reaches the upper
frequency, output ON signal.
The lower frequency arrival
(no output when shutdown)
When the operating frequency reaches the lower
frequency, output ON signal. The next stop status signal is
OFF.
Under voltage state output
When the inverter is in an undervoltage condition, output
ON signal.
Refer to the communication protocol.
Zero-speed operation 2
(shutdown also output)
The inverter’s output frequency is 0, output ON signal.
The signal is also ON when shutdown.
Cumulative power-on time
arrival
When the inverter's accumulated power on time (F6.08)
over F7.20 the set time, the output ON signal.
Frequency level detection
FDT2 output
Please refer to the function code F7.26, F7.27's
instructions.
Frequency 1 reaches output
Please refer to the function code F7.28, F7.29's instructions.
Frequency 2 reaches output
Please refer to the function code F7.30, F7.31's instructions.
Please refer to the function code F7.36, F7.37's instructions.
Please refer to the function code F7.38, F7.39's instructions.
When the timer function selection (F7.42) is valid, the
drive time to reach this run after the set time runs out,
output ON signal.
When the value of analog input AI1 greater than F7.51
(AI1 input protection limit) or less than F7.50 (AI1 input
protection under), output ON signal.
When the inverter is off-load state, output ON signal.
Inverter in reverse run, output ON signal
Refer to the description of function code F7.32, F7.33.
Module temperature reaches
Inverter module heatsink temperature (F6.06) reach the set
module temperature reaches value (F7.40), output signal
ON.
Please refer to the function code F7.34, F7.35's
instructions.
The lower frequency arrival
(stop and output)
When the operating frequency reaches the lower limit
frequency, output ON signal. In shutdown state of the
signal is also ON.
When the inverter failure, and the failure of the process to
continue to run mode, the inverter alarm output.
Motor over-temperature pre-
warning
When the motor temperature reaches F8.35 (motor
overheat pre-alarm threshold), the output ON signal.
(Motor temperature can be viewed at d0.41)
Current running time of
arrival
When the inverter starts running time is longer than the
time set by F7.45, it outputs ON signal.
High-speed pulse output
function selection
DA1 output function selection
DA2 output function selection
High-speed pulse output frequency range of 0.01kHz ~ F2.09 (high speed pulse output
maximum frequency), F2.09 can be set between 0.01kHz ~ 100.00kHz.