Chapter 5 Function parameter
49
Chapter 5
Before preforming asynchronous motor parameters comprehensive auto tuning, not only
motor type and motor nameplate parameters b0.00 to b0.05 must be set properly, but also encoder
type and encoder pulses b0.29, b0.28.
For asynchronous motor parameters comprehensive auto tuning, the inverter can obtain b0.06
to b0.10 five motor parameters, as well as the AB phase sequence b0.31 of encoder, vector control
current loop PI parameters F5.12 to F5.15.
5-1-16.y0 Function code management
Code
Parameter
name
Setting range
Factory
setting
Change
Limit
y0.00
Parameter
initialization
No operation
0
0
Restore the factory parameters, not including
motor parameters
1
Clear history
2
Restore default parameter values, including
motor parameters
3
Backup current user parameters
4
Restore user backup parameters
501
Clear keyboard storage area
10
Upload parameter to keyboard storage area 1
11
Upload parameter to keyboard storage area 2
12
Download the parameters from keyboard storage
1 area to the storage system
21
Download the parameters from keyboard storage
2 area to the storage system
22
1: restore the factory setting, not including motor parameters:after y0.00 is set to 1, most of the
inverter function parameters are restored to the factory default parameters, but motor parameters,
frequency command decimal point (F0.02), fault recording information, cumulative running time ,
cumulative power-on time and cumulative power consumption will not be restored.
2: clear history:to clear the history of the inverter's fault recording information, cumulative
running time , cumulative power-on time and cumulative power consumption.
3: restore default parameter values including motor parameters.
4: backup current user parameters:backup the parameters set by the current user. Backup all
function parameters. It is easy to restore the default settings when user incorrectly adjust
parameters.
501: store user backup parameters:Restore previous backup user parameters.
10: clear keyboard storage area:Empty keyboard storage area 1 and keyboard storage area 2
11: upload parameter to keyboard storage area 1:Upload the parameters of the inverter to
keyboard storage area 1.
12: upload parameter to keyboard storage area 2:Upload the parameters of the inverter to the
keyboard storage area 2.
21: download the parameters from keyboard storage 1 area to the storage system:Download
the parameters from keyboard storage 1 to inverter
22:download the parameters from keyboard storage 2 area to the storage system:Download the
parameters from keyboard storage 2 to inverter
5-1-17.y1 Fault query:
Code
Parameter name
Setting range
Factory
setting
Change
Limit