Appendix II
The first: Set F0.03 (main frequency source setting) as 0/1 (keyboard set frequency), and
then modify the settings frequency by modifying F0.01 (keyboard set frequency).
Communication mapping address of F0.01 is 0xF001 (Only need to change the RAM
communication mapping address to 0x0001).
The second :Set F0.03 (main frequency source setting) as 9 (Remote communication set),
and then modify the settings frequency by modifying (Communication settings). , mailing
address of this parameter is 0x1000.the communication set value is the percentage of the relative
value, 10000 corresponds to 100.00%, -10000 corresponds to -100.00%. For frequency
dimension data, it is the percentage of the maximum frequency (F0.19); for torque dimension
data, the percentage is F5.08 (torque upper limit digital setting).
Control command is input to the inverter: (write only)
0006: Deceleration and stop
Inverter read status: (read-only)
Parameter lock password verification: (If the return code is 8888H, it indicates that password
verification is passed)
Digital output terminal control: (write only)
BIT0: SPA output control
BIT1: RELAY2 output control
BIT2 RELAY1 output control
BIT3: Manufacturer reserves the undefined
BIT4: SPB switching quantity output control
Analog output DA1 control: (write only)
0 to 7FFF indicates 0% to 100%
Analog output DA2 control: (write only)
0 to 7FFF indicates 0% to 100%
SPB high-speed pulse output control: (write only)
0 to 7FFF indicates 0% to 100%
Inverter fault description:
Inverter fault information:
0000: No fault
0001: Inverter unit protection
0002: Acceleration overcurrent
0003: Deceleration overcurrent