Chapter 8 Maintenance and repair
8-1.Inspection and maintenance
During normal use of the inverter, in addition to routine inspections, the regular inspections are
required (e.g. the overhaul or the specified interval, and the interval shall not exceed 6 months),
please refer to the following table to implement the preventive measures.
Whether these phenomenon of
loose fastenings, overheat,
discharging, much dust, or
blocked air duct exist or not
"√" means routine or regular check to be needed
Do not disassemble or shake the device gratuitously during check, and never unplug the
connectors, otherwise the system will not run or will enter into fault state and lead to component
failure or even damage to the main switching device such as IGBT module.
The different instruments may come to different measurement results when measuring. It is
recommended that the pointer voltmeter shall be used for measuring input voltage, the rectifier
voltmeter for output voltage, the clamp-on ammeter for input current and output current, and the
electric wattmeter for power.
8-2.Parts for regular replacement
To ensure the reliable operation of inverter, in addition to regular care and maintenance, some
internal mechanical wear parts(including cooling fan, filtering capacitor of main circuit for energy
storage and exchange, and printed circuit board) shall be regularly replaced. Use and replacement for
such parts shall follow the provisions of below table, also depend on the specific application
environment, load and current status of inverter.