Chapter 5 Function parameter
35
Chapter 5
132.
F2.15
DO output terminal active status
selection
Units digit: SPB
switching quantity
0: positive logic
1: anti-logic
Tens digit: Relay 1
Hundreds digit:
Hundreds digit:
Undefined
Thousands digit: SPA
Ten thousands digit:
Relay 2
00000
133.
F2.16
DA1 zero bias coefficient
-100.0% to +100.0%
0.0%
134.
F2.17
DA1 gain
-10.00 to +10.00
1.00
135.
F2.18
DA2 zero bias coefficient
-100.0% to +100.0%
0.00%
136.
F2.19
DA2 gain
-10.00 to +10.00
1.00
5-1-5.F3 Group - Start and stop control group
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
137.
F3.00
Start-up mode
0: Direct startup
1: Speed tracking restart
2: Pre-excitation start (AC
asynchronous motor)
0
138.
F3.01
Speed tracking mode
0~2: reserve
3: Rotate speed tracking
method3
3
139.
F3.02
Speed tracking value
1 to 100
20
140.
F3.03
Start frequency
0.00Hz to 10.00Hz
0.00Hz
141.
F3.04
Hold time for start frequency
0.0s to 100.0s
0.0s
142.
F3.05
DC beforehand field current
0% to 100%
0%
143.
F3.06
DC excitation time beforehand
0.0s to 100.0s
0.0s
144.
F3.07
Stop mode
0: Deceleration
parking
1: Free
stop
0
145.
F3.08
DC Initial frequency
0.00Hz to F0.19 (maximum
frequency)
0.00
Hz
146.
F3.09
DC Waiting time
0.0s to 100.0s
0.0s
147.
F3.10
Stop DC braking current
0% to 100%
0%
148.
F3.11
Stop DC braking time
0.0s to 100.0s
0.0s
149.
F3.12
Braking utilization rate
0% to 100%
100%