Chapter 5 Function parameter
41
Chapter 5
251.
F7.48
Dormancy frequency
0.00Hz to awakens frequency(F7.46)
0.00Hz
252.
F7.49
Dormancy delay time
0.0s to 6500.0s
0.0s
253.
F7.50
AI1 input voltage
protection lower limit
0.00V to F7.51
3.1V
254.
F7.51
AI1 input voltage
protection upper limit
F7.50 to 10.00V
6.8V
255.
F7.52~
F7.53
Reserve
256.
F7.54
Jog mode setting3
Bits:
0: forward
1: reverse
2: determine the direction from the
main termina
Ten bits:
0: restore to the previous state after
jogging
1: stop running after jogging
Hundred bits:
0:recover to the previous deceleration
time after jogging
1: keep the deceleration time the
sameafter jogging
002
5-1-10.F8 Group - Fault and protection
No.
Code
Parameter name
Setting range
Factory
setting
Chang
e
257.
F8.00
Overcurrent stall gain
0 to 100
20
258.
F8.01
Overcurrent stall
protection current
100% to 200%
150%
259.
F8.02
Motor overload protection
selection
0: Invalid 1: Enable
1
260.
F8.03
Motor overload protection
gain
0.20 to 10.00
1.00
261.
F8.04
Motor overload pre-alarm
coefficient
50% to 100%
80%
262.
F8.05
Over-voltage stall gain
0 to 100
0
263.
F8.06
Over-voltage stall
protection voltage / energy
consumption brake
voltage
120% to 150%
130%
264.
F8.07
Input phase loss protection
Units digit:Input phase loss
11