Chapter 5 Function parameter
42
protection selection
0: Invalid 1: Enable
Tens digit:contactor actuation
protection
0: Invalid 1: Enable
Output phase loss
protection selection
Short to ground protection
Number of automatic fault
reset
Fault DO action selection
during automatic fault
reset
Automatic fault reset
interval
Over-speed detection
value
0.0 to 50.0% (maximum frequency)
Over-speed detection time
Detection value for too
large speed deviation
0.0 to 50.0% (maximum frequency)
Detection time for too
large speed deviation
Fault protection action
selection 1
Units digit: Motor overload (Err.11)
0: Free stop
1: Stop at the selected mode
2: Continue to run
Tens digit: input phase loss (Err.12)
(same as units digit)
Hundred digit: output phase loss
(Err.13) (same as units digit)
Thousand digit: external fault
(Err.15) (same as units digit)
Ten thousands digit: Communication
abnormal(
Err.16
)(same as units
digit)
Fault protection action
selection 2
Units digit: Encoder fault(Err.20)
0: Free stop
1:Switch to V/F and then stop at the
selected mode
2:Switch to V/F and continue to run
Tens digit: function code read and
write abnormal (Err.21)
0: Free stop
1: Stop at the selected mode
Hundreds digit: Reserved
Thousands digit: Motor overheating