Chapter 5 Function parameter
43
Chapter 5
(Err.45) ( same as F8.17 units digit)
Ten thousands digit: Running time
arrival(Err.26)(same as F8.
17 units
digit)
276.
F8.19
Fault protection action
selection 3
Units digit:User-defined fault
1(Err.27) (same as F8.17 units digit)
Tens digit:User-defined fault
2(Err.28) (same as F8.17 units digit)
Hundreds digit: Power-on time
arrival (Err.29) ( same as F8.17 units
digit)
Thousands digit: Load drop (Err.30)
0: Free stop
1: stop at select mode
2:Deceleration to 7% of the rated
motor frequency and then continue
running, automatically return to the
set frequency to run if the load drop
does not happen.
automatically return to the set
frequency to run if the load drop does
not happen.
automatically restore to the set
frequency for when the load drop
does not happen.
Ten thousands digit: PID feedback
loss when running (Err.31) (same as
F8.17 units digit)
00000
277.
F8.20
Fault protection action
selection 4
Units digit: Too large speed deviation
(Err.42) ( same as F8.17 units digit)
Tens digit: Motor over-speed (Err.43)
Hundreds digit: Initial position error
(Err.51)
( same as F8.17 units digit)
Thousands digit: Reserved Ten
thousands digit: Reserved
00000
278.
F8.21~
F8.23
Reserve
279.
F8.24
Fault running frequency
0: current frequency running
1: setting frequency running
2: upper frequency running
3: down frequency running
4: Abnormal reserve frequency
running
0
280.
F8.25
Abnormal reserve
frequency
60.0% to 100.0%
90%
281.
F8.26
Momentary power cut
action selection
0: Invalid
1: Deceleration
2: Deceleration and stop
0.50s