Chapter 5 Function parameter
45
Chapter 5
298.
F9.07
Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
5-1-12.FA Group - Torque control parameters
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
299.
FA.00
Speed/torque control mode
selection
0: speed control 1: torque
control
0
300.
FA.01
Torque setting source selection
under torque control mode
0: keyboard setting (FA.02)
1: Analog AI1 setting
2: Analog AI2 setting
3: Panel potentiometer setting
4: High-speed pulse setting
5: Communications reference
6: MIN (AI1, AI2)
7: MAX (AI1, AI2)
8.
High-speed pulse setting
0
301.
FA.02
Torque figures setunder torque
control mode
-200.0% to 200.0%
150%
302.
FA.03
Torque control acceleration time
0.00s to 650.00s
0.00s
303.
FA.04
Torque control deceleration time
0.00s to 650.00s
0.00s
304.
FA.05
Torque control forward
maximum frequency
0.00Hz to F0.19(maximum
frequency)
50.00
Hz
305.
FA.06
Torque control backward
maximum frequency
0.00Hz to F0.19 (maximum
frequency)
50.00
Hz
306.
FA.07
Torque filter time
0.00s to 10.00s
0.00s
5-1-13.FB Group - Control optimization parameters
No.
Code
Parameter name
Setting range
Factory
setting
Chang
e
307.
FB.00
Fast current limiting manner
0: Invalid 1: enable
1
308.
FB.01
Under-voltage point setting
50.0% to 140.0%
100.0%
309.
FB.02
Over-voltage point setting
200.0V to 2500.0V
810V
310.
FB.03
Deadband compensation
mode selection
0: no compensation
1: compensation mode 1
2: compensation mode 2
1
311.
FB.04
Current
detection
compensation
0 to 100
5
312.
FB.05
Vector optimization without PG
mode selection
0:
no optimization
1: optimization mode 1
2: optimization mode 2
1

Table of Contents