EasyManua.ls Logo

Powtran PI500 series - Virtual DI, Virtual DO (E3.00 - E3.21)

Powtran PI500 series
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Function parameter
50
Chapter 5
400.
E2.16
Proportional gain KP2
0.0 to 200.0
20.0
401.
E2.17
Integration time Ti2
0.01s to 10.00s
2.00s
402.
E2.18
Differential time Td2
0.00 to 10.000
0.000s
403.
E2.19
PID parameter switching
conditions
0:
no switching
1:
switching via terminals
2:
automatically switching
according to deviation.
0
404.
E2.20
PID parameter switching
deviation 1
0.0% to E2.21
20.0%
405.
E2.21
PID parameter switching
deviation 2
E2.20 to 100.0%
80.0%
406.
E2.22
PID integral properties
Units digit: integral separation
0: Invalid; 1: Valid
Tens digit: whether stop integration
when output reaches limit
0: continue; 1: stop
00
407.
E2.23
PID initial value
0.0% to 100.0%
0.0%
408.
E2.24
PID initial value hold time
0.00s to 360.00s
0.00s
409.
E2.25
Maximum deviation of twice
outputs(forward)
0.00% to 100.00%
1.00%
410.
E2.26
Maximum deviation of twice
outputs(backward)
0.00% to 100.00%
1.00%
411.
E2.27
Computing status after PID
stop
0: stop without computing
1: stop with computing
1
412.
E2.28
reserved
413.
E2.29
PID automatic decrease
frequency selection
0invalid1valid
0
414.
E2.30
PID stop frequency
0.00Hz~maximum
frequency(F0.19)
25
415.
E2.31
PID checking time
0s~3600
s
10
416.
E2.32
PID checking times
10~500
20
5-1-18.E3 Group Virtual DIVirtual DO
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
417.
E3.00
Virtual VDI1 terminal function
selection
0 to 50
0
418.
E3.01
Virtual VDI2 terminal function
selection
0 to 50
0

Table of Contents