Chapter 5 Function parameter
64
Chapter 5
Multi-speed
6
Simple PLC
7
PID
8
Communications reference
9
Tens digit
Terminal block command binding frequency
source selection (0 to 9, same as units digit)
Hundreds
digit
Communication command binding frequency
source selection (0 to 9, same as units digit)
Define the combination of 3 operation command channels and 9 frequency reference
channels for easily synchronously switching.
The principle for above frequency source reference channel is same as frequency source
master setting selection F0.03, please see the description of F0.03 function code. The different
running command channel can be bundled with the same frequency reference channel. When
command source has the available frequency source for bundling, in the valid period of command
source , the set frequency source by F0.03 to F0.07 is no longer valid.
F0.13
Acceleration time 1
0.0s~6500s
-
F0.14
Deceleration time 1
0.0s~6500s
-
Acceleration time refers to the required time when the inverter accelerates from zero
frequency to F0.16.
Deceleration time refers to the required time when the inverter decelerates from F0.16 to zero
frequency.
PI500 provides four groups of ac/deceleration time, user can select by using the digital input
terminal DI, as follows:
The first group: F0.13, F0.14; The third group: F7.10, F7.11;
The second group: F7.08, F7.09; The fourth group: F7.12, F7.13.
F0.15
Ac/Deceleration time unit
1 second
0
1
0.1 second
1
0.01 second
2
To meet the demand of the various on-site, PI500 provides three kinds of time unit: 1 second,
0.1 second and 0.01 second respectively.
Note: when modifying the function parameters, the number of decimal places that the four
groups of ac/deceleration time displayed will change displayed, the ac/deceleration time will
change accordingly.
F0.16
Ac/deceleration time reference
frequency
Maximum frequency(F0.19)
0
0
Set frequency
1
100Hz
2
Ac/deceleration time refers to the required time from zero frequency to F0.16 or from F0.16
to zero frequency.
When F0.16 selects 1, the ac/deceleration time depends on the set frequency, if the set
frequency change frequently, and the acceleration of the motor is varied, please use with caution.
F0.17
Carrier frequency adjustment as
per temperature
NO
0
0
YES
1
The adjustment of carrier frequency refers to that the inverter automatically adjusts the carrier
frequency according to the radiator temperature, so as to reduce the carrier frequency .when the
radiator temperature rises, and to restore the carrier frequency when the radiator temperature
reduces.
F0.18
Carrier Frequency
0.5kHz to 16.0kHz
-
This function is mainly used for improving the noise and vibration phenomena that the
inverter operation may occur If the carrier frequency is higher, there are more ideal current
waveform and less motor noise. It is very applicable in the place to be muted. But at this time, the
switching loss of main components is large, the whole unit fevers, the efficiency decreases and the
output reduces. At the same time, there is a bigger radio interference, another problem is that the
capacitive leakage current increases when running at the high carrier frequency, the equipped