Chapter 5 Function parameter
66
conversion of the motor rotation direction.
Tip: after the parameter is initialized, the motor running direction will be restored to its
original status. When the system debugging is completed, please use with caution where the
change of motor steering is strictly prohibited.
G type (constant torque load type)
F type (fans/pumps load type)
The parameters is only for user to view the factory model and can not be changed.
1: Suitable for constant torque load 2: Suitable for variable torque load (fans, pumps load)
5-2-3.Input terminal:F1.00-F1.46
PI500 series inverter comes standard with eight multifunctional digital input terminals (where
DI5 can be used as high-speed pulse input terminal), three
analog
input terminals.
DI1 terminal function selection
DI2 terminal function selection
DI3 terminal function selection
DI4 terminal function selection
DI5 terminal function selection
DI6 terminal function selection
DI7 terminal function selection
DI8 terminal function selection
These parameters are used to set the digital multi-function input terminal, the optional
functions are shown in the following table:
The terminal for not use can be set to "no function" to prevent
accidental operation.
External terminals are used to control the FWD/REV run mode
of inverter.
Three-wire operation
control
This terminal is used to determine the inverter's three-wire
control mode. For details, please refer to the instructions of
function code F1.10 ("terminal command mode).
FJOG means Forward JOG running, RJOG means Reverse JOG
running. For Jog running frequency and Jog Ac/deceleration
time, please refer to the description of the function code F7.00,
F7.01, F7.02.
Modify frequency increment/decrement command when the
frequency is referenced by external terminal. Adjust up/down the
set frequency when the digital setting is selected as the
frequency source.
The inverter output is blocked, at the time, the parking process
of motor is not controlled by the inverter. This way is same as
the principle of free stop described in F3.07.
The function make use of terminal for fault reset. It has same
function with RESET key on the keyboard. This function can be
used to realize remote fault reset.