Chapter 5 Function parameter
77
Current running time of
arrival
When the inverter starts running time is longer than the time
set by F7.45, it outputs ON signal.
High-speed pulse output function selection
DA1 output function selection
DA2 output function selection
High-speed pulse output frequency range of 0.01kHz ~ F2.09 (high speed pulse output
maximum frequency), F2.09 can be set between 0.01kHz ~ 100.00kHz.
Analog Output DA1 and DA2 output range is 0V ~ 10V, or 0mA ~ 20mA. Pulse output or
analog output range, with the corresponding scaling function relationship in the following table:
0~2 times the motor rated current
0~2 times the motor rated toqure
0~1.2 times inverter rated voltage
0~Max. output frequency correspondent speed
0.0A~100.0A(Inverter power≦55kW);
0.0A~1000.0A(Inverter power>55kW)
Frequency source main set
Maximum frequency of high-speed pulse
When the SPB terminal as a pulse output, the function code is used to select the maximum
output pulse frequency value.
Relay 1 output delay time
Expansion card DO output delay time
Relay 2 output delay time
Set the output terminal SPA, SPB, relay 1, relay 2, delay time of changing from the state
produced to the actual output differentiated.
DO terminal
active status
selection
SPB switching active status selection
Relay 1 active setting (0 to 1, as
defined in units digit)
SPA Terminal active state settings
(0 to 1, as defined in units digit)
Relay 2 active setting (0 to 1, as
defined in units digit)