Chapter 5 Function parameter
42
Chapter 5
supply at the same time, when the water supply pressure is greater than the pump pressure display
value and the frequency is lower than the pump reduction frequency, after the pump delay time is
reduced, the inverter performs the pump reduction operation. Afterwards if the pressure is still
high, the pump will continue to be reduced, achieving a rapid adjustment function, and it is
intended to supplement the shortcomings of the pressure instability when the water supply load of
the conventional water supply system is abrupt.
285
E8.15
Start pump number
1 to 8
Select the pump number that the inverter starts to run. 1 corresponds to motor A and 2
corresponds to motor B. (Note: the pump number must be the inverter motor. If this parameter is
changed, the inverter will automatically set the corresponding motor as the inverter motor).
286
E8.16
Low pressure alarm
0 to 16.00Mbars
After the inverter runs E8.48 time, if the pressure is still less than this value, the inverter
reports ERR_46 fault.
287
E8.17
Ultra-high pressure offset
0 to 16.00Mbars
Used to set the super high pressure display value in linkage(Ultra high pressure value display
=Set pressure +Ultra-high pressure offset)
288
E8.18
Ultra high pressure value display
0 to 16.00Mbars
After the inverter runs E8.49 time, if the pressure still exceeds this value, the inverter reports
ERR_47 fault.
289
E8.19
Sleep function
0: Invalid 1: Valid
Select whether the sleep function is valid or invalid. The sleep and wake-up functions are
related to F7.46~F7.49. Details of the F7 group parameters.
290
E8.20
Sleep pressure offset
0 to 16.00Mbars
Used to set the sleep pressure display value in linkage(Sleep pressure display value =Set
pressure +Sleep pressure offset)
291
E8.21
Actual value of dormancy pressure
0 to 16.00Mbars
The sleep function is associated with F7.48 and F7.49. If the pressure is greater than the
actual value of the sleep pressure and the current frequency is less than or equal to the sleep
frequency (F7.48), after the sleep delay time (F7.49), the inverter enters the sleep state.
292
E8.22
Offset under wake-up pressure
0 to 16.00Mbars
Used to link the welcome pressure display value(Wake up pressure display value =Set
pressure Wake-up pressure offset)
293
E8.23
Actual value of wake-up pressure
0 to 16.00Mbars
The wake-up function is associated with F7.46, F7.47. If the pressure is less than the actual
value of the wake-up pressure, and the currently calculated frequency is less than or equal to the
wake-up frequency (F7.46), after the wake-up delay time (F7.47), the inverter cancels the sleep.
status.
294
E8.24
Motor A attribute
0: Invalid 1: Frequency conversion
2: Power frequency
295
E8.25
Motor B attribute
0: Invalid 1: Frequency conversion
2: Power frequency
296
E8.26
Motor C attribute
0: Invalid 1: Frequency conversion
2: Power frequency
297
E8.27
Motor D attribute
0: Invalid 1: Frequency conversion
2: Power frequency
298
E8.28
Motor E attribute
0: Invalid 1: Frequency conversion