Chapter 8 Maintenance and repair
65
8-5.Measuring and readings
※ If a general instrument is used to measure current, imbalance will exists for the current at
theinput terminal. generally, the deviation is not more than 10%, that is normal. If the
deviationexceeds 30%, please inform the original manufacturer to replace rectifier bridge, or
check ifthe deviation of three-phase input voltage is above 5V or not.
※ If a general multi-meter is used to measure three-phase output voltage, the reading is not
accurate due to the interference of carrier frequency and it is only for reference.