Section V. Function parameter table
H13
7 step time T7 0.0~3200.0 s 2.0 Y
H14
acc. time at1 0.1~3200.0 s 10.0
Y
H15
dec. time dt1 0.1~3200.0 s 10.0
Y
H16
acc. time at2 0.1~3200.0 s 10.0
Y
H17
dec. time dt2 0.1~3200.0 s 10.0
Y
H18
acc. time at3 0.1~3200.0 s 10.0
Y
H19
dec. time dt3 0.1~3200.0 s 10.0
Y
H20
acc. time at4 0.1~3200.0 s 10.0
Y
H21
dec. time dt4 0.1~3200.0 s 10.0
Y
H22
acc. time at5 0.1~3200.0 s 10.0
Y
H23
dec. time dt5 0.1~3200.0 s 10.0
Y
H24
acc. time at6 0.1~3200.0 s 10.0
Y
H25
dec. time dt6 0.1~3200.0 s 10.0
Y
H26
acc. time at7 0.1~3200.0 s 10.0
Y
H27
dec. time dt7 0.1~3200.0 s 10.0
Y
Forward 0
H28
Multi-step speed 1
running direction
Reverse 1
- 0 Y
Forward 0
H29
Multi-step speed 2
running direction
Reverse 1
- 0 Y
Forward 0
H30
Multi-step speed 3
running direction
Reverse 1
- 0 Y
Forward 0
H31
Multi-step speed 4
running direction
Reverse 1
- 0 Y
Forward 0
H32
Multi-step speed 5
running direction
Reverse 1
- 0 Y
Forward 0
H33
Multi-step speed 6
running direction.
Reverse 1
- 0 Y
Forward 0
H34
Multi-step speed 7
running direction
Reverse 1
- 0 Y
5-2-3. F69 I/O group [I/O]
Ref
LCD keyboard
explanation
Range of set value Unit
Factory
setting
Y/N
o00
V2 input filter time
2~200 ms
10 Y
Section V. Function parameter table
o01
V2 min. input voltage
0.00~o02 V 0.00
Y
o02
V2 max. input
voltage
o01~10.00 V 10.00
Y
o03
I input filter time 2~200 ms
10 Y
o04
I input min. current
0.00~o05 mA
0.00
Y
o05
I input max. current
o04~20.00 mA
20.00
Y
No Function 0
Set frequency 1
Actual frequency 2
Actual current 3
Output voltage 4
Bus voltage 5
IGBT temperature 6
Output power 7
Output speed 8
o06
*o07
DA1 Ouput
Reserved
*reserved 9
-
-
0
-
Y
-
o08
DA1 output lower
adjustment
0~o09 % 0.0 Y
o09
DA1 output upper
adjustment
o08~100.0 % 100.0
Y
*o10
reserved
- - - -
*o11
reserved
- - - -
*o12
reserved - - - -
No function 0
Fault alarm 1
Over current inspection 2
Over load inspection 3
Over voltage inspection 4
Lack voltage inspection 5
Low load inspection 6
Over heat inspection 7
Running state with command
8
*reserved
9
o13
*o14
*o15
*o16
o17
*o18
O.P. signal sel. 1
*reserved
*reserved
*reserved
O.P. signal sel. 5
* reserved
Motor reverse 10
-
-
-
-
-
-
0
-
-
-
0
-
Y
-
-
-
Y
-