Section VI. Function Parameter Description
setting
frequency
forward
reverse
command
FOR
REV
stop braking (forward and reverse rotate)
time
time
setting
frequency
output
frequency
braking
frequency
stop braking time
ON
setting
frequency
output
frequency
braking
frequency
RUN
STOP
braking
frequency
stop braking time
time
time
stop braking (run state)
start up braking
RUN
STOP
output
frequency
start up braking
ON
time
F27: Stop mode set factory setting: 0
When receiving “stop” command, it sets the stop mode according to this
parameter.
0: Deceleration stop mode, according to the deceleration time set by this
parameter, inverter decelerates to the lowest frequency and stops.
1: Free stop mode. “Stop” command to the inverter, it stops output, motor
runs free until stops due to the effects of load inertia.
Section VI. Function Parameter Description
F28: Jog acceleration time factory setting: 1.0s
F29: Jog deceleration time factory setting: 1.0s
Jog acceleration time defines the same step acceleration/deceleration.
f29
f28
Max frequency
time
JOG frequency
0
Actual jog time equals to the set acc/dec time multiples a time multiple
which is decided by the tens digit of F56. Please refer to F56.
F30: Jog direction set factory setting: 0
0: Forward
1: Reverse
F31: Jog frequency set factory setting: 6.00/60.0Hz
Jog frequency setting range is from lower limit frequency to upper limit
frequency.
F32: Traverse running frequency f1 factory setting: 40.00/400.0Hz
F33: Traverse running frequency f2 factory setting: 20.00/200.0Hz
F34: Traverse running difference △f factory setting: 2.00/20.0Hz
F35: Traverse running timing T1 factory setting: 2.0s
F36: Traverse running timing T2 factory setting: 2.0s
Calculating acceleration/deceleration time with f1、f2、△f、T1、T2.
f
f
f
fff
T1T2
T2
T1
T1
time
decelerate
traverse f2
accelerate
traverse f1
running
instruction
time
output frequency
F37: Skip frequency 1 factory setting: 0.00/0.0Hz
F38: Skip frequency 2 factory setting: 0.00/0.0Hz