Section VI. Function Parameter Description
F57: Percentage in energy saving running factory setting: 100%
frequency (Hz)
output voltatge (V)
100%
75%
This parameter is for minimum output voltage percentage in energy saving
running For constant torque running, inverter can calculate the optimized
output voltage to the load according to the load state. Calculation is invalid
during acceleration or deceleration. This function is to save energy by lower
the output voltage and enhance the frequency factors, this parameter
confirms the minimum reduced output voltage; if the parameter is set 100%,
the energy saving running mode is closed.
If energy saving is effective, inverter’s actual voltage output value=inverter’s
rated output voltage × output voltage percentage × energy saving output
voltage percentage.
F58: FDT frequency set 1 factory setting: 0.00/0.0Hz
F59: FDT frequency set 2 factory setting:0.00/0.0Hz
time
time
time
ON OFF
ON
OFF
OFF
ON
OFF
ON
output frequency
FDT frequency
setting 1 arrived
FDT1=35Hz
FDT2=30Hz
FDT frequency
level detect
ON express signal action; OFF express no signal action
When output signal select(o13-o17) 14, inverter’s output frequency
arrives or accesses FDT frequency set 1, output signal terminal actions;
inverter’s output frequency is lower than the set frequency, output signal
does not action.
When output signal select(o13-o17) 15,firstly FDT frequency set 1
inspected, inverter’s output frequency arrives or accesses FDT frequency
Section VI. Function Parameter Description
set 1, output signal terminal actions; after terminal action, FDT frequency
set 2 inspected, inverter’s output frequency is lower than FDT frequency
set 2, output signal terminal does not action.
e.g. FDT frequency set 1 is 35Hz, FDT frequency set 2 is 30Hz, output
signal terminal actions as above:
F60: Frequency inspection range factory setting: 0.00/0.0Hz
This parameter defines frequency inspection range for adjusting I/O output
function: 11 set frequency reaching the inspection range.
F61: Load type factory setting: 0
The parameter defines the load type, the system automatically adjust the
parameters according to the load type to satisfy different requirement of
different load. Please inquir Powtran technician to select the right load type.
Wrong load type may damage the equipment.
0: general
1: pump
2: Blower fan
3: Plastic jetting mould machine
4: Braiding machine
5: Hoister
6: Pumping jack
7: Belt conveyor
*8~14: Reserved
F62: Terminal control modes factory setting: 0
0: standard running control
1: 2-point running control
2: 3-point running control
e.g.: Standard running control
FWD/ STOP
REV/ STOP
COM
REV (edge trigger: reverse in falling edge,
and stop in rising edge
level trigger: reverse in closed state,
and stop in open state)
FWD (edge trigger: forward in falling edge,
and stop in rising edge
level trigger: forward in closed state,
and stop in open state)
e.g.: 2-point running control