Section VI. Function Parameter Description
o05=20mA
I2
V2
Voltage/Current
0Hz
o05o02
0V/0mA
setted frequency
o04o01
maximum frequency
10V/20mA
o06:DA1 output terminal factory setting: 0
*o07: Reserved
Value Output
Output signal range
0 No Function
No output
1 Set frequency
0~max frequency
2 Actual frequency
0~max frequency
3 Actual current
G:2 times of rated current
4 Output voltage
0~1.35 times of rated output
5 Bus voltage
0~1.35 times of bus voltage
6 IGBT temperature
0~80.0℃
7 Output power
0~200%
8 Output speed
0~max rotating speed
9 *Reserved
-
o08: DA1 output lower adjustment factory setting: 0.0%
o09: DA1 output upper adjustment factory setting: 100.0%
*o10~o11: Reserved
Valtage/current
100.0%
50.0%
corresponding
max output
frequency
10.0%
10V/20mA
20.0%
0V/0mA
100.0%
0Hz
DA1
corresponding
max output
frequency
Valtage/current
DA1
0Hz
0V/0mA
10V/20mA
It is to set lower and upper DA1/DA2 output signal.
e.g. DA1 1-5V Output voltage o08=10.0%, o09=50.0%
DA2 4-20mA Output current o10=20.0%, o11=100.0%
Section VI. Function Parameter Description
Note: Each output terminal with 2 selection: voltage output (0~10V) and
current output (0~20mA), the default selection is voltage output. Selecting
voltage output, short circuit DA1V of JP4 (on the control card); selecting
current output, short circuit DA1C of JP4 (on the control card).
*o12: Reserved.
o13: Output signal selection 1 factory setting: 0
*o14~ o16: Reserved
o17: Output signal selection 5 factory setting: 0
*o18: Reserved
Display
LED set value
0 No function
1 Fault alarm
2 Over current inspection
3 Over load inspection
4 Over voltage inspection
5 Lack voltage inspection
6 Low load inspection
7 Over heat inspection
8 Running state with command
9 *Reserved
10 Motor reverse
11 Set frequency arrival
12 Upper limit frequency
13 Lower limit frequency
14 FDT frequency 1 arrival
15 FDT frequency level inspection
16 0 speed running
17 Position arrival
18 *Reserved
19 Program running 1 cycle finished
20 Speed pursue mode inspection