Section VI. Function Parameter Description
21 Running state without command
22 Inverter reverse command
23 Deceleration running
24 Acceleration running
25 *Reserved
26 *Reserved
27 Inverters rated current arrival
28 Motors rated current arrival
29 Input lower frequency arrival
30 FDT frequency set 2 arrival
31 *Reserved
32 *Reserved
o19: Minimum input frequency factory setting: 0.00/0.0Hz
o20: Maximum input frequency factory setting: 50.00/500.0Hz
Define the connection of analog input and frequency, o19 is anolog V2, I2
sets the frequency to minimum voltage/current; o20 is V2, I2 sets the
frequency to maximum voltage/current, the connection is effective when
F04 is 1, 2, and 3.
If o19<o20, it is positive input, if o19>o20, it is negative input.
If V2 inputs 1~5V voltage, 0.00~50.00Hz, parameters are set as below:
O01=1V, o02=5V, O19=0.00Hz, o20=50.00Hz.
If V2 inputs 4~20mA current, 45.00~30.00Hz, the parameters are set as
below:
O04=4mA,o05=20Ma, o19=45.00Hz, o20=30.00Hz
o19 0Hz
o20 50Hz
0Hz
o19 45Hz
o20 30Hz
o04 o05
I2
o01 o02
V2
setted
frequency
setted
frequency
Current
Voltage
*6-2-4. F70 Current loop parameters [CUR] Reserved
*6-2-5. F70 speed-loop parameter [SPD] Reserved
*6-2-6. F72 PID parameter [PID] Reserved
Section VI. Function Parameter Description
6-2-7. F73 System parameter [SYS]
y00: restore factory setting factory setting: 0
0: not restore
1: restore
When the parameter is valid, all the parameters will restore the setting value
before factory.
Those parameters which have no factory value will reserve the setting
value.
y01: Fault record 1
y02: Fault record 2
y03: Fault record 3
y04: Fault record 4
y05: Fault record 5
These parameters register fault which happen in the last several times, and
can inquire about the value of monitor object at the time of fault by PRG
and plus or minutes key.
The monitor object of fault state:
0: fault style
The fault code is expressed as following:
Serial number
LED display
Fault message
0 OC_C Over current signal from current inspected circuit
1 OCFA Over current signal from drive circuit.
2 OC_2
Output over current
, OC protection when current exceeds
motors 2 times of rated current
3 OU over voltage
4 OL over load
5 - *Reserved
6 OH over heat
7 LU under voltage
8 UL under load
9 EEPr EEPROM error
10 OC_P System is disturbed or impacted by instant over current
11 E_FL external fault
12 - *Reserved
13 - *Reserved
14 DATE Time limit fault