Chapter5.Function parameter
30
10
Run pause
The inverter slows down and stops, but all
operating parameters are memorized. Such as
PLC parameters, PID parameters. This terminal
signal disappears, the inverter reverts to the
previous state of running before parking.
11
External fault normally
open input
When the signal is sent to the inverter, inverter
trips fault Err.15, and performs troubleshooting
according to fault protection action (details refer
to function code F8.17)
Option 12 ~ 51omitted, If more choices needed, pleasecontact us.
F1.10
Terminal command mode
Two-wire type 1
0
0
Two-wire type 2
1
Three-wire type 1
2
Three-wire type 2
3
This parameter defines four different modes to control inverter operation through external
terminals.
0: Two-wire type 1
This mode is the most commonly used two-wire mode. The forward/reverse
operation of motor is determined by terminal DIx, DIy.
The terminal function is set as follows:
Terminals
Set value
Description
DIx
1
Forward run (FWD)
DIy
2
Reverse run (REV)
Of which, DIx and DIy are the multi-function input terminals of DI1 to DI10, the
level is active.
1: Two-wire type 2
In the mode, DIx terminal is used as running enabled, while DIy terminal is used to
determine running direction.
The terminal function is set as follows:
Terminals
Set value
Description
DIx
1
Forward run (FWD)
DIy
2
Reverse run (REV)
K1
0
0
1
1
K2
0
1
0
1
Command
Stop
p
REV
Stop
FWD
K2
K1
DIx
Forward
(FWD)
DIy
Reverse
(REV)
COM
Digital common
terminals
Two-wire mode
1