Chapter8.Installation and Spare Circuit
72
Function description of main circuit terminal
Connect to three-phase power
supply, single-phase connects to R,
T;PV voltage connects to R, T
Braking resistor
terminals
Connect to braking resistor
Connect to three-phase motor
Connect to DC reactor(remove the
shorting block)
Description of control circuit terminals
External+
10V power
supply
Output +10V power supply, maximum
output current: 10mA
Generally it is used as power supply of
external potentiometer, potentiometer
resistance range: 1kΩ to 5kΩ
External+24V
power supply
Output +24V power supply, generally it is
used as power supply of digital input and
output terminals and external sensor.
Maximum output current: 200mA
External
power input
terminal
When external signal is used to drive,
please unplug J5 jumpers ,
PLC
must be
connected to external power supply, and to
+24V (default).
1.Input range:(DC 0V to 10V/0 to 20mA),
depends on the selected J3 jumper on
control panel.
2.Input impedance: 22kΩ with voltage
input, 500Ω with current input.
1.Input range:(DC 0V to 10V/0 to 20mA),
depends on the selected J4 jumper on
control panel.
2.Input impedance: 22kΩ with voltage
input, 500Ω with current input.
1.Opto-coupler isolation, compatible with