Chapter 5 Function parameter
114
38
Alarm output
When the inverter occurs failure and
continues to run, the inverter alarms output.
39
Motor
overtemperature pre-
warning
3
When the motor temperature reaches
F8.35 (motor overheat pre-alarm threshold),
the output ON signal. (Motor temperature by
d0.41 view)
40
Current running time
arrival
Outputs ON signal when the inverter's
current running time exceeds the set time by
F7.45.
F2.06
High-speed pulse output
function selection
0 to 17
0
F2.07
DA1 output function
selection
0 to 17
0
F2.08
DA2 output function
selection
0 to 17
1
High-speed pulse output frequency range is 0.01kHz to F2.09 (maximum frequency of
high-speed pulse output), F2.09 can be set between 0.01kHz to 100.00kHz.
Analog output DA1 and DA2 output range is 0V to 10V, or 0mA to 20mA. The range of
pulse output or analog output and the corresponding calibration relation are shown in the
following table:
Set
value
Function
Description
0
Running frequency
0 to maximum output frequency
1
Set frequency
0 to maximum output frequency
2
Output current
0 to 2 times rated motor current
3
Output torque
0 to 2 times rated motor torque
4
Output power
0 to 2 times rated power
5
Output voltage
0 to 1.2 times rated inverter voltage
6
High-speed pulse
input
0.01kHz to 100.00kHz
7
AI1
0V to 10V
8
AI2
0V to 10V (or 0 to 20mA)
9
Reserve
10
Length
0 to maximum set length
11
Count value
0 to maximum count value
12
Communication
setting
0.0% to 100.0%
13
Motor speed
0 to speed with maximum output
frequency
14
Output current
0.0A to 100.0A (inverter power
55kW); 0.0A to 1000.0A (inverter power>
55kW)
15
DC bus voltage
0.0V to 1000.0V