Chapter 5 Function parameter
145
Stop at the selected mode
Decelerate to 7% of the rated
frequency of motor and continue
to run, automatically return to the
set frequency to run if the load
drop does not happen.
PID feedback loss when
running(Fault ID
Err.31
)( same as F8.17
units digit)
Fault
protection
action
selection 4
Too large speed
deviation(Fault ID
Err.42
)( same as F8.17
units digit)
Motor overspeed(Fault
ID
Err.43
)( same as
F8.17 units digit)
Initial position
error(Fault ID
Err.51
)( same as F8.17
units digit)
When "free stop" is selected, the inverter displays Err. *, and directly stops.
When "Stop at the selected mode" is selected, the inverter displays Arr. *, firstly
stops at the selected mode and then displays Err. * When "continue to run" is selected, the
inverter continues to run and displays Arr. *, the operating frequency is set by F8.24.
Continue
running
frequency
selection
when failure
happens
Running at current frequency
Running at upper limit frequency
Running at lower limit frequency
Running at abnormal spare
frequency
When the inverter occurs faults during operation, and the troubleshooting mode for
the fault is set to "continue to run", the inverter displays Arr. *, and runs at the operating