This feature means that when the momentary power cut happens or the voltage
suddenly reduces, the drive will reduce the output speed to compensate the reduced value
of the inverter DC bus voltage by using load feedback energy, in order to maintain the
inverter to continue running.
If F8.26 = 1, when the momentary power cut happens or the voltage suddenly
reduces, the inverter will decelerate, when the bus voltage is back to normal, the inverter
will normally accelerate to the set frequency to run. To determine whether the bus voltage
returns to normal or not, check whether the bus voltage is normal and lasts for longer than
the set time by F8.28.
If F8.26 = 2, when the momentary power cut happens or the voltage suddenly
reduces, the inverter will decelerate till to stop.