VDO and DO output function is similar,can be used in conjunction with VDIx,to
achieve some simple logic control .
When VDOx output function is 0, output status is decided by DI1~DI5 input status on
the control board, VDOx and Dix one-to-one correspondence.
When the output function selection is not 0, VD0x function setting and using method is
same as D0 in F2 output parameter, please read F2 group parameter description.
The VDOx output valid status can be set by E3.16 setting, select positive logic or anti-
logic.
5-2-19.Motor parameters: b0.00-b0.35
General asynchronous
motor
Asynchronous inverter
motor
Permanent magnet
synchronous motor
0.01A to 655.35A (inverter
power ≦ 55kW)
0.1A to 6553.5A (inverter rate>
55kW)
0.01Hz to F0.19 (maximum
frequency)
Above b0.00 to b0.05 are the motor nameplate parameters, which affects the accuracy of
the measured parameters. Please set up according to the motor nameplate parameters. The
excellent vector control performance needs the accurate motor parameters. The accurate
identification of parameters is derived from the correct setting of rated motor parameters.
In order to guarantee the control performance, please configure your motor according to
the inverter standards, the motor rated current is limited to between 30% to 100% of the
inverter rated current. The motor rated current can be set, but can not exceed the inverter