Chapter 5 Function parameter
59
No.
Code
Parameter
name
Setting range
Factory
setting
Chan
ge
Reference
page
266.
F8.10
Number of
automatic fault
reset
0 to 32767
0
142
267.
F8.11
Fault DO action
selection during
automatic fault
reset
0: OFF
1: ON
0
143
268.
F8.12
Automatic fault
reset interval
0.1s to 100.0s
1
.
0s
143
269.
F8.13
Overspeed
detection value
0.0 to 50.0% (maximum
frequency)
20.0%
143
270.
F8.14
Overspeed
detection time
0.0 to 60.0s
1.0s
143
271.
F8.15
Detection value
for too large
speed deviation
0.0 to 50.0% (maximum
frequency)
20.0%
143
272.
F8.16
Detection time
for too large
speed deviation
0.0 to 60.0s
5.0s
143
273.
F8.17
Fault protection
action selection
1
Units digit: Motor overload
(Err.11)
0: Free stop
1: Stop at the selected
mode
2: Continue to run
Tens digit: input phase loss
(Err.12) (same as units
digit)
Hundred digit: output
phase loss (Err.13) (same
as units digit)
Thousand digit: external
fault (Err.15) (same as
units digit)
Ten thousands digit:
Communication
00000
143