function input terminals UP, DOWN) on the keyboard, adjust directly on the basis of master
frequency source.
2) When the frequency source auxiliary setting is set to analog input reference (AI1,
AI2, panel potentiometer) or pulse input reference, the frequency source auxiliary setting
range for the set 100% can be set by F0.05 and F0.06.
3) When the frequency source is set to pulse input reference, it is similar to analog
reference . Tip: Both master and auxiliary setting of frequency source can not be set in the
same channel, ie F0.03 and F0.04 can not be set as the same value, otherwise easily lead to
confusion.
When the frequency source is set to "frequency overlay"(i.e. F0.07 is set to 1, 3 or 4),
these two parameters are used to determine the range of adjustment of frequency source
auxiliary setting.
F0.05 is used to determine the object corresponding to frequency source auxiliary
setting range, either the maximum frequency or the frequency source master setting, If the
frequency source master setting 1 is selected, so the frequency source auxiliary setting range
will be subject to the change of the frequency source master setting, it applies for when
auxiliary setting range is less than master setting range; If the frequency source master setting
2 is selected, so the frequency source auxiliary setting range will be subject to the change of
the frequency source master setting, it applies for when auxiliary setting range is more than
master setting range;
Recommendation: frequency source master setting (F0.03) shall adopt analog setting,
frequency source auxiliary setting (F0.04) shall adopt digital setting.